Height | 28 mm |
Width | 28 mm |
Depth | 79 mm |
Ambient temperature (operation) | -40 °C ... 80 °C (non-Ex) |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Degree of protection | IP67 |
Housing material | Stainless steel |
Color | silver |
Standards for cearances and creepage distances | IEC 60664-1 |
IEC 60079-11 | |
Mounting type | M20 |
Type | Screw-in module |
Number of positions | 2 |
Direction of action | Line-Line & Line-Earth Ground |
IEC test classification | C1 |
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 36 V DC |
25 V AC | |
Operating effective current IC at UC | ≤ 5 µA |
Residual current IPE | ≤ 2 µA |
Nominal discharge current In (8/20) µs (Core-Core) | 260 A |
Nominal discharge current In (8/20) µs (core-earth) | 10 kA |
Pulse discharge current Iimp (10/350) µs | 1 kA |
Total discharge current Itotal (8/20) µs | 20 kA |
Total discharge current Itotal (10/350) µs | 2 kA |
Max. discharge current Imax (8/20) µs maximum (Core-Core) | 260 A |
Max. discharge current Imax (8/20) µs maximum (Core-Earth) | 20 kA |
Nominal pulse current Ian (10/1000) µs (Core-Core) | 50 A |
Output voltage limitation at 1 kV/µs (core-core) spike | ≤ 130 V |
Output voltage limitation at 1 kV/µs (core-earth) spike | ≤ 1.1 kV |
Output voltage limitation at 1 kV/µs (core-core) static | ≤ 60 V |
Voltage protection level Up (core-core) | ≤ 65 V (C3 - 10 A) |
Voltage protection level Up (core-ground) | ≤ 1.1 kV (C3 - 100 A) |
≤ 1.1 kV (C1 - 1 kV/500 A) | |
≤ 1.2 kV (C2 - 10 kV / 5 kA) | |
Response time tA (core-core) | ≤ 1 ns |
Response time tA (core-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.1 dB (30 MHz / 50 Ω) |
typ. 0.1 dB (6 MHz / 150 Ω) | |
Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 70 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 40 MHz |
Capacity (core-core) | typ. 20 pF |
Capacity (core-earth) | typ. 5 pF |
Surge protection fault message | none |
Impulse durability (conductor-conductor) | C3 - 25 A |
Impulse durability (conductor-ground) | C1 - 1 kV/500 A |
C2 - 10 kV/5 kA | |
C3 - 100 A | |
D1 - 1 kA | |
Alternating current carrying capacity (conductor-ground) | 10 A - 1 s |
Connection method | Individual wires |
Standards/specifications | EN 61643-21 A2:2013 |
EN 60079-0 2012 | |
EN 60079-1 2007 | |
EN 60079-11 2012 | |
EN 60079-31 2009 | |
IEC 60079-0 2011 | |
IEC 60079-1 2007 | |
IEC 60079-11 2011 | |
IEC 60079-31 2008 |
Maximum inner capacitance Ci | 1.65 nF |
Max. internal inductance Li | 1 µH |
Max. input current Ii | 500 mA (T4 / ≤ 75 °C) |
500 mA (T5 / ≤ 75 °C) | |
500 mA (T6 / ≤ 60 °C) | |
max. input voltage Ui | 36 V DC |
max. input power Pi | 3 W |
Insulation voltage to ground | 500 V AC |
Ambient temperature (operation) | -40 °C ... 75 °C (T4) |
-40 °C ... 75 °C (T5) | |
-40 °C ... 60 °C (T6) |
ATEX | II 1 G Ex ia IIC T4...T6 |
II 2 G Ex d IIC T4...T6 | |
II 1 D Ex iaD 20 IP6x T85 °C...135 °C | |
II 2 D Ex tD A21 IP6x T85 °C...135 °C | |
IECEx | Ga Ex ia IIC T4...T6 |
Ex d IIC T4...T6 | |
Ex iaD IP6x T85 °C...135 °C | |
Ex tD A21 IP6x T85 °C...135 °C |
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
No hazardous substances above threshold values |
eCl@ss 4.0 | 27140201 |
eCl@ss 4.1 | 27130801 |
eCl@ss 5.0 | 27130801 |
eCl@ss 5.1 | 27130801 |
eCl@ss 6.0 | 27130807 |
eCl@ss 7.0 | 27130807 |
eCl@ss 8.0 | 27130807 |
eCl@ss 9.0 | 27130807 |
ETIM 2.0 | EC000943 |
ETIM 3.0 | EC000943 |
ETIM 4.0 | EC000943 |
ETIM 5.0 | EC000943 |
ETIM 6.0 | EC000943 |
UNSPSC 6.01 | 30212010 |
UNSPSC 7.0901 | 39121610 |
UNSPSC 11 | 39121610 |
UNSPSC 12.01 | 39121610 |
UNSPSC 13.2 | 39121620 |