range of product | Altistart 48 | |
product or component type | Soft starter | |
product destination | Asynchronous motors | |
product specific application | Heavy duty industry and pumps | |
device short name | ATS48 | |
[Us] rated supply voltage | 230...415 V (- 15...10 %) | |
motor power kW | 55 kW at 230 V (connection in the motor supply line) for standard applications 90 kW at 230 V (connection to the motor delta terminals) for severe applications 90 kW at 400 V (connection in the motor supply line) for severe applications 110 kW at 230 V (connection to the motor delta terminals) for standard applications 110 kW at 400 V (connection in the motor supply line) for standard applications 132 kW at 400 V (connection to the motor delta terminals) for severe applications 160 kW at 400 V (connection to the motor delta terminals) for standard applications 45 kW at 230 V (connection in the motor supply line) for severe applications |
|
power dissipation in W | For severe applications 468 W For standard applications 580 W |
|
utilisation category | AC-53A | |
type of start | Start with torque control (current limited to 5 In) | |
IcL starter rating | 210 A (connection in the motor supply line) for severe applications 364 A (connection to the motor delta terminals) for severe applications 364 A (connection to the motor delta terminals) for standard applications 210 A (connection in the motor supply line) for standard applications |
|
IP degree of protection | IP00 |
assembly style | With heat sink | |
function available | External bypass (optional) | |
supply voltage limits | 195...456 V | |
supply frequency | 50...60 Hz (- 5...5 %) | |
network frequency | 47.5...63 Hz | |
device connection | In the motor supply line To the motor delta terminals |
|
factory setting current | 195 A | |
[Uc] control circuit voltage | 220 - 15 % to 415 + 10 %, 50/60 Hz | |
control circuit consumption | 50 W | |
discrete output number | 2 | |
discrete output type | (LO1) logic output 0 V common configurable (LO2) logic output 0 V common configurable (R1) relay outputs fault relay NO (R2) relay outputs end of starting relay NO (R3) relay outputs motor powered NO |
|
output absolute accuracy precision | +/- 5 % | |
minimum switching current | Relay outputs 10 mA at 6 V DC | |
maximum switching current | Logic output 0.2 A at 30 V DC Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5, L/R = 20 ms Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5, L/R = 20 ms |
|
discrete input number | 5 | |
discrete input type | PTC, 750 Ohm at 25 °C (Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm |
|
discrete input voltage | 24 V (<= 30 V) | |
discrete input logic | Positive logic (Stop, Run, LI3, LI4) state 0 < 5 V and <= 2 mA, state 1 > 11 V and >= 5 mA | |
supply inrush current | Adjustable 0.4...1.3 Icl | |
analogue output type | (AO) current output 0-20 mA or 4-20 mA <= 500 Ohm | |
communication port protocol | Modbus | |
connector type | 1 RJ45 | |
communication data link | Serial | |
physical interface | RS485 multidrop | |
transmission rate | 4800, 9600 or 19200 bps | |
installed device | 31 | |
protection type | Phase failure (line) Thermal protection (motor) Thermal protection (starter) |
|
marking | CE | |
type of cooling | Forced convection | |
operating position | Vertical +/- 10 degree | |
height | 380 mm | |
width | 320 mm | |
depth | 265 mm | |
product weight | 18.2 kg | |
power range | 30...50 kW at 200...240 V 3 phases 55...100 kW at 380...440 V 3 phases 55...100 kW at 200...240 V 3 phases 110...220 kW at 380...440 V 3 phases 110...220 kW at 200...240 V 3 phases |
|
motor starter type | Soft starter |
electromagnetic compatibility | Conducted and radiated emissions conforming to IEC 60947-4-2 level A Damped oscillating waves conforming to IEC 61000-4-12 level 3 Electrostatic discharge conforming to IEC 61000-4-2 level 3 Immunity to electrical transients conforming to IEC 61000-4-4 level 4 Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3 level 3 Voltage/current impulse conforming to IEC 61000-4-5 level 3 |
|
standards | EN/IEC 60947-4-2 | |
product certifications | CCC CSA C-Tick DNV GOST NOM 117 SEPRO TCF UL |
|
vibration resistance | 1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6 |
|
shock resistance | 15 gn for 11 ms conforming to EN/IEC 60068-2-27 | |
noise level | 54 dB | |
pollution degree | Level 3 conforming to IEC 60664-1 | |
relative humidity | 0...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 | |
ambient air temperature for operation | 40...60 °C with current derating of 2 % per °C -10...40 °C without derating |
|
ambient air temperature for storage | -25...70 °C | |
operating altitude | <= 1000 m without derating > 1000...2000 m with current derating of 2.2 % per additional 100 m |
Warranty period | 18 months |