Lovato DMG610 là Đồng hồ điện đa năng LCD 100-440AC 120-250DC RS485 72X46
Flush-mount LCD multimeter, expandable, backlight icon LCD display, 72X46mm/2.8X1.8”, auxiliary supply 100-440VAC/120-250VDC, front optical port and RS485 port
-
Type of product: Multifunction digital metering instruments
-
Type of installation: Flush mounting
-
Type of current connection: CT /5A /1A
-
Accuracy active energy measurement: Class 1 (IEC/EN 62053-21)
-
Reactive energy: Class 2 (IEC/EN 62053-23)
-
Current harmonic analysis: 15th order
-
Built-in communication port: RS485
-
Expandable: Yes
Order code |
DMG610 |
Weight [g] |
320 |
Qty. per package |
1 |
Multiple qty. of packs per order |
1 |
Package dimensions [mm] |
124X104X076 |
Volume [cm³] |
980.096 |
Bar code [EAN13] |
8013975211151 |
HS Code |
90303100 |
Thông số kỹ thuật DMG610
Product designation |
|
Flush-mount LCD multimeters. expandable |
Product type designation |
|
DMG610 |
Type |
|
Three-phase + neutral |
Auxiliary supply Us |
Auxiliary rated supply voltage AC |
VAC |
100…440 |
Auxiliary rated supply voltage DC |
VDC |
120…250 |
Auxiliary operating voltage range |
|
AC |
|
|
min |
VAC |
90 |
|
|
Max |
VAC |
484 |
|
DC |
|
|
min |
VDC |
93.5 |
|
|
Max |
VDC |
300 |
Operational frequency |
|
|
min |
Hz |
45 |
|
|
max |
Hz |
66 |
Power consumption |
|
|
Max |
VA |
9.5 |
Power dissipation Max |
W |
3.5 |
Measuring voltage inputs |
Rated voltage (Ue) |
|
|
phase-phase |
VAC |
600 |
|
|
phase-neutral |
VAC |
300 |
Operating voltage range |
|
|
phase-phase |
VAC |
50…720 |
|
|
phase-neutral |
VAC |
30…360 |
Voltage inputs operational frequency |
|
|
min |
Hz |
45 |
|
|
max |
Hz |
66 |
Voltage inputs measurement method |
|
True RMS |
Connection method |
|
Single. two. three-phase with or without neutral. balanced three-phase system |
Current inputs |
Rated current (Ie) |
A |
1A/5A |
Measurement range |
|
0.01…1.2 / 0.01…6 |
Measurement method |
|
TRMS |
Overload capacity |
|
+20% Ie by external CT with 5A secondary |
Overload peak |
A |
50A for 1s |
Accuracy |
|
|
VLN voltage |
|
±0.5% |
|
|
VLL voltage |
|
±0.5% |
|
|
Current |
|
±0.5% |
|
|
Frequency |
|
±0.05% |
|
|
Active power |
|
±0.5% |
|
|
Active energy |
|
Class 1 (IEC/EN 62053-21) |
|
|
Reactive energy |
|
Class 2 (IEC/EN 62053-23) |
RS485 serial interface |
Baud rate |
bps |
Programmable 1200…115200 |
Insulations |
Rated insulation voltage Ui IEC/EN |
V |
600 |
Rated impulse withstand voltage Uimp |
kV |
9.5 |
Operating frequency withstand voltage |
kV |
5.2 |
Functions |
Harmonic analysis |
|
15th order |
PLC logic |
|
No |
Type of communication port |
|
RS485 |
Ethernet-RS485 gateway function |
|
No |
Mechanical features |
Housing type |
|
Polyamide |
Terminals type |
|
Removable |
Conductor cross section |
|
|
min |
mm² |
0.2 |
|
|
Max |
mm² |
2.5 |
|
|
min |
AWG |
24 |
|
|
Max |
AWG |
12 |
Tightening torque (Max) |
|
|
|
Nm |
0.5 |
|
|
|
lbin |
4.5 |
Fixing |
|
Flush-mounting |
Weight |
g |
350 |
Ambient conditions |
Temperature |
|
Operating temperature |
|
|
min |
°C |
-20 |
|
|
max |
°C |
+60 |
|
Storage temperature |
|
|
min |
°C |
-30 |
|
|
max |
°C |
+80 |
Relative humidity |
% |
<90 |
Maximum Pollution degree |
|
2 |
Protection degree |
|
IP54 |
ETIM classification |
ETIM 8.0 |
|
EC002301 - Multifunction measuring instrument |
- Tài liệu kỹ thuật Lovato DMG610
ở đây.