Order code | DMG610 |
---|---|
Weight [g] | 320 |
Qty. per package | 1 |
Multiple qty. of packs per order | 1 |
Package dimensions [mm] | 124X104X076 |
Volume [cm³] | 980.096 |
Bar code [EAN13] | 8013975211151 |
HS Code | 90303100 |
Product designation | Flush-mount LCD multimeters. expandable | |||
Product type designation | DMG610 | |||
Type | Three-phase + neutral | |||
Auxiliary supply Us | ||||
Auxiliary rated supply voltage AC | VAC | 100…440 | ||
Auxiliary rated supply voltage DC | VDC | 120…250 | ||
Auxiliary operating voltage range | ||||
AC | ||||
min | VAC | 90 | ||
Max | VAC | 484 | ||
DC | ||||
min | VDC | 93.5 | ||
Max | VDC | 300 | ||
Operational frequency | ||||
min | Hz | 45 | ||
max | Hz | 66 | ||
Power consumption | ||||
Max | VA | 9.5 | ||
Power dissipation Max | W | 3.5 | ||
Measuring voltage inputs | ||||
Rated voltage (Ue) | ||||
phase-phase | VAC | 600 | ||
phase-neutral | VAC | 300 | ||
Operating voltage range | ||||
phase-phase | VAC | 50…720 | ||
phase-neutral | VAC | 30…360 | ||
Voltage inputs operational frequency | ||||
min | Hz | 45 | ||
max | Hz | 66 | ||
Voltage inputs measurement method | True RMS | |||
Connection method | Single. two. three-phase with or without neutral. balanced three-phase system | |||
Current inputs | ||||
Rated current (Ie) | A | 1A/5A | ||
Measurement range | 0.01…1.2 / 0.01…6 | |||
Measurement method | TRMS | |||
Overload capacity | +20% Ie by external CT with 5A secondary | |||
Overload peak | A | 50A for 1s | ||
Accuracy | ||||
VLN voltage | ±0.5% | |||
VLL voltage | ±0.5% | |||
Current | ±0.5% | |||
Frequency | ±0.05% | |||
Active power | ±0.5% | |||
Active energy | Class 1 (IEC/EN 62053-21) | |||
Reactive energy | Class 2 (IEC/EN 62053-23) | |||
RS485 serial interface | ||||
Baud rate | bps | Programmable 1200…115200 | ||
Insulations | ||||
Rated insulation voltage Ui IEC/EN | V | 600 | ||
Rated impulse withstand voltage Uimp | kV | 9.5 | ||
Operating frequency withstand voltage | kV | 5.2 | ||
Functions | ||||
Harmonic analysis | 15th order | |||
PLC logic | No | |||
Type of communication port | RS485 | |||
Ethernet-RS485 gateway function | No | |||
Mechanical features | ||||
Housing type | Polyamide | |||
Terminals type | Removable | |||
Conductor cross section | ||||
min | mm² | 0.2 | ||
Max | mm² | 2.5 | ||
min | AWG | 24 | ||
Max | AWG | 12 | ||
Tightening torque (Max) | ||||
Nm | 0.5 | |||
lbin | 4.5 | |||
Fixing | Flush-mounting | |||
Weight | g | 350 | ||
Ambient conditions | ||||
Temperature | ||||
Operating temperature | ||||
min | °C | -20 | ||
max | °C | +60 | ||
Storage temperature | ||||
min | °C | -30 | ||
max | °C | +80 | ||
Relative humidity | % | <90 | ||
Maximum Pollution degree | 2 | |||
Protection degree | IP54 | |||
ETIM classification | ||||
ETIM 8.0 | EC002301 - Multifunction measuring instrument |