Whether installed in the intake and exhaust fans of air-conditioning systems, in pumps for heating and cooling circuits, or in compressors for refrigeration units: SINAMICS G120P converters are ideally suited to meet every requirement of building management systems.
Stay flexible: Due to their IP20 and IP55 degrees of protection, the PM230 Power Modules can not only be installed in the control cabinet, but can also be directly at the machine. And thanks to different EMC filters, they can be used both in the public power grid and in industrial networks.
A well-thought-out portfolio: Apart from standard functions such as setpoint specifications, on/off switching logic, protection and monitoring of machine, motor and converter, SINAMICS G120P also offers numerous industry-specific functions. These include the regulation of two or multiple zones and one fire protection mode which ensures the longest possible operation in an emergency.
- Full control – Real-time clock with exact time stamp for error and warning logging, max. buffer time five days, automatic summer / winter changeover
- Freely programmable – Digital timers for the control of three selectable events depending on the weekday / hour / minute
SINAMICS G120P in the Building Technologies: |
|
---|---|
Power: |
0,37 - 90 kW |
Voltage: |
3 AC 380 - 480 V |
Control procedure: |
U/f control with stator flux orientation, vector control without encoder |
Growing complexity of plants and globalization of markets: The drives of the SINAMICS G120P series always have the right answer for the special features of the process industry.
Usable and available worldwide – SINAMICS G120P is ready to meet your global requirements. And with the key functions of speed control, controlling range, efficiency and communication level, it ensures simple operation.
Thanks to the upgraded PM330 Power Modules, you now have a complete series of SINAMICS G120P products at your disposal: in all sizes and across all voltage ranges, from 400 V to 690 V. A flexibly applicable and consistent approach, which minimizes your configuration and implementation overheads.
The new PM240P-2 Power Modules increases your process reliability: with integrated safety functionality up to the SIL3 level.
- Process reliability – Utmost safety level thanks to Integrated safety functions, safe electronic switch-off (Safe Torque-off / Safe Stop 1)
- Robustness – Even for special operating conditions such as temperatures ranging from -10° C to 60° C and aggressive environments (resistance to pollutants)
- Cost saving – Increased energy efficiency with higher output voltage (98 %) through integrated dc link reactor
- Enhanced flexibility – due to the new voltage level up to 690 V
- Saving space – allows compact control cabinets
- Robustness – through numerous functions such as output voltage sensing
- Total integration – the complete product series is available
SINAMICS G120P in the Process industry |
|
---|---|
Power: |
11 - 630 kW |
Voltage: |
3 AC 380 - 480 V and 3 AC 500 - 690 V |
Control procedure: |
U/f control with stator flux orientation, vector control without encoder |
Power Modules for industrial applications and building technology
Control Units have been especially designed for pump, fan, compressor applications
Supplementary system components for SINAMICS G120P
Low harmonic effects, low apparent current consumption, high power factor
IP55 degree of protection for direct on-site setup, longer cables possible due to reactors, operation of motors with low voltage strength via optional filters
Operation at ambient temperatures up to 60 °C
Integrated filters for use in public power grids and industrial environments
PM230 Power Modules in an IP20 degree of protection are available in six frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 0,37 … 75 kW
PM230 Power Modules in an IP55 degree of protection are available in six frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 0,37 … 90 kW
Using the SINAMICS G120P Cabinet units in degrees of protection IP20 up to IP54, the power range for wall-mounting devices can be increased up to 110 ... 630 kW.
Process reliability: highest level of safety thanks to integrated safety functions and safe electronic shutdown (Safe Torque-Off / Safe Stop 1)
Robustness: also suitable for tougher environmental conditions such as temperatures from -10 °C to +60 °C and aggressive atmospheres (resistance to harmful substances)
Energy saving: increased energy efficiency with higher output voltage (98 percent) due to integrated DC link reactor
PM240P-2 Power Modules in an IP20 degree of protection are available in three frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 22 … 132 kW
3AC500 ... 690 V +/-10%, 11 ... 132 kW
Greater flexibility – with a new voltage level up to 690 V
Space-saving – facilitates compact control cabinets
Robustness – due to numerous functions such as output voltage recording
Integration – complete product range available
PM330 Power Modules in an IP20 degree of protection are available in two frame sizes in the following voltage and power range:
3AC380 … 480 V +/-10%, 160 … 560 kW
3AC500 ... 690 V +/-10%, 315 ... 630 kW
PM230 Power Modules are designed for applications involving pumps, fans and compressors with a quadratic characteristic. They do not have an integrated braking chopper (single-quadrant applications).
The PM230 Power Module only generates low line harmonics and apparent power losses. In addition to the energy-related advantages, the environmental stress is also reduced.
Frame sizes FSA to FSF of the PM230 Power Module in degree of protection IP55 are available with integrated line filter class A for installations acc. to Category C2 and in accordance with EN 61800‑3. The PM230 Power Modules with integrated filter class B that are available as an alternative also comply with the conducted interference requirements for Category C1 in accordance with EN 61800‑3.
Frame sizes FSA to FSF of the PM230 Power Module in degree of protection IP20 are available with integrated line filter class A for Category C2 installations in accordance with EN 61800‑3, or without an integrated line filter.
The frame sizes FSA to FSC of the PM230 Power Module with degree of protection IP20, Push Through version, are available with integrated line filter class A for installations acc. to Category C2 as per EN 61800‑3 or without an integrated line filter.
PM230 Power Modules with integrated line filter class A or class B meet the EMC limit values up to a maximum cable length of 25 m (82 ft) with shielded cables between inverter and motor.
Unfiltered PM230 Power Modules with degree of protection IP20 with external line filter class B comply with EMC Category C1 with a cable length of 50 m (164 ft) between the converter and the motor. EMC Category C2 is complied with through the use of an additional output reactor for a cable length of 150 m (492 ft) (see output-side power components).
The line system configurations that are supported are symmetrical systems with grounded neutral point.
PM230 Power Modules in frame sizes FSA to FSC can be combined with the CU240E‑2 Control Unit 1). This enables the implementation of the STO safety function acc. to SIL 2.
PM230 Power Modules, frame sizes FSD to FSF, do not support Control Units with Safety Integrated. Safety functions can be implemented here by means of external switching devices.
1) More information on the CU240E‑2 Control Unit is available in Catalog D 31, Chapter SINAMICS G120. An adapter, article number 10055500 (ordered from and supplied by KnorrTec at www.knorrtec.com), is required to operate a PM230 Power Module with degree of protection IP55 in combination with a CU240E‑2 Control Unit and an IOP/BOP-2.
Note:
Shield plates and shield connection kits are available. These can be used in the wiring installation for the Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information, see Shield connection kits and shield plates for Control Units and Power Modules in section Supplementary system components.
PM230 Power Modules have the following connections and interfaces:
PM230 Power Modules communicate with the Control Unit via the PM-IF interface.
Connection diagram for PM230 Power Module with or without integrated line filter class A or B
The following line-side and load-side power components are optionally available in the appropriate frame sizes for the Power Modules:
|
Frame size |
|||||
---|---|---|---|---|---|---|
|
FSA |
FSB |
FSC |
FSD |
FSE |
FSF |
PM230 Power Module (IP54/IP55) |
||||||
Available frame sizes |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
Line-side power components |
||||||
Line filter class A |
I |
I |
I |
I |
I |
I |
Line filter class B |
I |
I |
I |
I |
I |
I |
Line reactor 1) |
– 1) |
– 1) |
– 1) |
– 1) |
– 1) |
– 1) |
Load-side power components |
||||||
Output reactor |
S |
S |
S |
S |
S |
S |
Sine-wave filter |
– |
– |
– |
S |
S |
S |
PM230 Power Module (IP20) |
||||||
Available frame sizes |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
Line-side power components |
||||||
Line filter class A |
F |
F |
F |
F |
F |
F |
Line filter class B |
U 2) |
U 2) |
U 2) |
S |
S |
S |
Line reactor 1) |
– 1) |
– 1) |
– 1) |
– 1) |
– 1) |
– 1) |
Load-side power components |
||||||
Output reactor |
S |
S |
S |
S |
S |
S |
Sine-wave filter |
– |
– |
– |
S |
S |
S |
U = Base component
S = Lateral mounting
I = Integrated
F = Power Modules available with and without integrated filter class A
– = Not possible
1) A line reactor is not required and must not be used in conjunction with a PM230 Power Module.
2) Lateral mounting is the only possible option for Push Through variants.
The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result in the following maximum cable lengths:
|
Maximum permissible motor cable lengths (shielded/unshielded) in m (ft) |
|||||
---|---|---|---|---|---|---|
Frame size |
FSA |
FSB |
FSC |
FSD |
FSE |
FSF |
PM230 Power Module, degree of protection IP20 |
||||||
Available frame sizes |
✓ |
✓ |
✓ |
✓ |
✓ |
✓ |
Without output reactor/sine-wave filter |
25/100 (82/328) |
25/100 (82/328) |
25/100 (82/328) |
25/100 (82/328) |
25/100 (82/328) |
25/100 (82/328) |
With optional output reactor |
|
|
|
|
|
|
|
150/225 (492/738) |
150/225 (492/738) |
150/225 (492/738) |
– |
– |
– |
|
100/150 (328/492) |
100/150 (328/492) |
100/150 (328/492) |
– |
– |
– |
|
– |
– |
– |
200/300 (656/984) |
200/300 (656/984) |
200/300 (656/984) |
With optional sine-wave filter |
|
|
|
|
|
|
|
– |
– |
– |
200/300 (656/984) |
200/300 (656/984) |
200/300 (656/984) |
With integrated line filter class A |
|
|
|
|
|
|
|
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
With optional external line filter class B (EMC category C1 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800‑3) |
|
|
|
|
|
|
|
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
50/- (164/-) |
With optional external line filter class B and output reactor (EMC category C2 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800‑3) |
|
|
|
|
|
|
|
150/- (492/-) |
150/- (492/-) |
150/- (492/-) |
– |
– |
– |
|
100/- (328/-) |
100/- (328/-) |
100/- (328/-) |
– |
– |
– |
1) Additional information is available on the Internet at http://www.siemens.com/sinamics-g120/documentation
|
PM230 Power Modules |
|
---|---|---|
Degree of protection |
IP55 (with BOP‑2 or blanking cover) |
IP20/UL Open Type |
Power (low overload LO) |
0.37 ... 90 kW |
0.37 ... 75 kW |
Rated output current (low overload LO) |
1.3 ... 178 A |
1.3 ... 145 A |
Power (high overload HO) |
0.25 ... 75 kW |
0.25 ... 55 kW |
Rated output current (high overload HO) |
0.9 ... 145 A |
0.9 ... 110 A |
System operating voltage |
380 ... 480 V ±10 % 3 AC |
|
Grid requirement |
>100 |
|
Input frequency |
47 ... 63 Hz |
|
Output frequency |
|
|
|
0 ... 550 Hz |
|
|
0 ... 240 Hz |
|
Pulse frequency |
4 kHz |
|
Power factor λ |
0.9 |
|
Output voltage, max. as % of input voltage |
95 % |
|
Overload capability |
|
|
|
Note: When the overload capability is used, the base-load current IL is not reduced. |
|
|
1.5 × base-load current IL (i. e. 150 % overload) for 3 s plus |
|
|
1.1 × base-load current IL (i. e. 110 % overload) for 60 s within a cycle time of 300 s |
|
|
Note: When the overload capability is used, the base-load current IH is not reduced. |
|
|
2 × base-load current IH (i. e. 200 % overload) for 3 s plus |
|
|
1.5 × base-load current IH (i. e. 150 % overload) for 60 s within a cycle time of 300 s |
|
Electromagnetic compatibility |
|
|
Possible braking methods |
DC braking |
|
Operating temperature |
|
|
|
Frame sizes FSA to FSC: -10 ... +40 °C (14 ... 104 °F) without derating >40 ... 60 °C (104 ... 140 °F) see derating characteristics |
|
|
Frame sizes FSA to FSC: -10 ... +50 °C (14 ... 122 °F) without derating >50 ... 60 °C (122 ... 140 °F) see derating characteristics |
|
Relative humidity |
<95 %, condensation not permissible |
|
Storage temperature |
-40 ... +70 °C (-40 ... +158 °F) |
|
Cooling |
Power units with increased air cooling using integrated fans |
|
Installation altitude |
Up to 1000 m (3281 ft) above sea level without derating, |
|
Protection functions |
|
|
Rated short-circuit current SCCR (Short-Circuit Current Rating) 3) |
Frame sizes FSA to FSC: 40 kA |
65 kA |
Compliance with standards |
UL 1), cUL 2), CE, RCM, SEMI F47 |
|
CE marking |
According to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU |
1) For degree of protection IP55/UL Type 12, the UL approval only applies to frame sizes FSA to FSC.
2) Applies to PM230 Power Modules, frame sizes FSA to FSC.
3) Applies to industrial control panel installations acc. to NEC Article 409 or UL 508A/508C.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules, degree of protection IP55/UL Type 12 |
|||||
---|---|---|---|---|---|---|
With integrated line filter class A |
6SL3223-0DE13-7AG1 |
6SL3223-0DE15-5AG1 |
6SL3223-0DE17-5AG1 |
6SL3223-0DE21-1AG1 |
6SL3223-0DE21-5AG1 |
|
With integrated line filter class B |
6SL3223-0DE13-7BG1 |
6SL3223-0DE15-5BG1 |
6SL3223-0DE17-5BG1 |
6SL3223-0DE21-1BG1 |
6SL3223-0DE21-5BG1 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
1.3 |
1.7 |
2.2 |
3.1 |
4.1 |
|
A |
1.3 |
1.7 |
2.2 |
3.1 |
4.1 |
|
A |
0.9 |
1.3 |
1.7 |
2.2 |
3.1 |
|
A |
2 |
2.6 |
3.4 |
4.7 |
6.2 |
Rated power |
|
|
|
|
|
|
|
kW |
0.37 |
0.55 |
0.75 |
1.1 |
1.5 |
|
kW |
0.25 |
0.37 |
0.55 |
0.75 |
1.1 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
86 |
90 |
92 |
94 |
95 |
Power loss 3) at rated current |
kW |
0.04 |
0.043 |
0.047 |
0.055 |
0.064 |
Cooling air requirement |
m3/s (ft3/s) |
0.007 (0.25) |
0.007 (0.25) |
0.007 (0.25) |
0.007 (0.25) |
0.007 (0.25) |
Sound pressure level LpA (1 m) |
dB |
61.9 |
61.9 |
61.9 |
61.9 |
61.9 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
|
A |
1.3 |
1.8 |
2.3 |
3.2 |
4.2 |
|
A |
0.9 |
1.3 |
1.8 |
2.3 |
3.2 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
Motor cable length, max. 5) |
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection 6) |
|
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
154 (6.06) |
154 (6.06) |
154 (6.06) |
154 (6.06) |
154 (6.06) |
|
mm (in) |
460 (18.11) |
460 (18.11) |
460 (18.1) |
460 (18.11) |
460 (18.1) |
|
|
|
|
|
|
|
|
mm (in) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
|
mm (in) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
Frame size |
|
FSA |
FSA |
FSA |
FSA |
FSA |
Weight, approx. |
kg (lb) |
4.3 (9.48) |
4.3 (9.48) |
4.3 (9.48) |
4.3 (9.48) |
4.3 (9.48) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.
6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules, degree of protection IP55/UL Type 12 |
|||||
---|---|---|---|---|---|---|
With integrated line filter class A |
6SL3223-0DE22-2AG1 |
6SL3223-0DE23-0AG1 |
6SL3223-0DE24-0AG1 |
6SL3223-0DE25-5AG1 |
6SL3223-0DE27-5AG1 |
|
With integrated line filter class B |
6SL3223-0DE22-2BG1 |
6SL3223-0DE23-0BG1 |
6SL3223-0DE24-0BG1 |
6SL3223-0DE25-5BG1 |
6SL3223-0DE27-5BG1 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
5.9 |
7.7 |
10.2 |
13.2 |
18 |
|
A |
5.9 |
7.7 |
10.2 |
13.2 |
18 |
|
A |
4.1 |
5.9 |
7.7 |
10.2 |
13.2 |
|
A |
8.9 |
11.8 |
15.4 |
20.4 |
27 |
Rated power |
|
|
|
|
|
|
|
kW |
2.2 |
3 |
4 |
5.5 |
7.5 |
|
kW |
1.5 |
2.2 |
3 |
4 |
5.5 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
96 |
96 |
97 |
97 |
97 |
Power loss 3) at rated current |
kW |
0.086 |
0.11 |
0.137 |
0.173 |
0.235 |
Cooling air requirement |
m3/s (ft3/s) |
0.007 (0.25) |
0.007 (0.25) |
0.009 (0.32) |
0.009 (0.32) |
0.009 (0.32) |
Sound pressure level LpA (1 m) |
dB |
61.9 |
61.9 |
62.8 |
62.8 |
62.8 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
|
A |
6.1 |
8 |
11 |
14 |
19 |
|
A |
4.2 |
6.1 |
8 |
11 |
14 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
2.5 ... 6 |
4 ... 6 |
4 ... 6 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
2.5 ... 6 |
4 ... 6 |
4 ... 6 |
Motor cable length, max. 5) |
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection 6) |
|
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
154 (6.06) |
154 (6.06) |
180 (7.09) |
180 (7.09) |
180 (7.09) |
|
mm (in) |
460 (18.11) |
460 (18.11) |
540 (21.26) |
540 (21.26) |
540 (21.26) |
|
|
|
|
|
|
|
|
mm (in) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
|
mm (in) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
Frame size |
|
FSA |
FSA |
FSB |
FSB |
FSB |
Weight, approx. |
kg (lb) |
4.3 (9.48) |
4.3 (9.48) |
6.3 (13.9) |
6.3 (13.9) |
6.3 (13.9) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.
6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules, degree of protection IP55/UL Type 12 1) |
||||||
---|---|---|---|---|---|---|---|
With integrated line filter class A |
6SL3223-0DE31-1AG1 |
6SL3223-0DE31-5AG1 |
6SL3223-0DE31-8AG1 |
– |
6SL3223-0DE32-2AA0 |
6SL3223-0DE33-0AA0 |
|
With integrated line filter class B |
6SL3223-0DE31-1BG1 |
6SL3223-0DE31-5BG1 |
– |
6SL3223-0DE31-8BA0 |
6SL3223-0DE32-2BA0 |
6SL3223-0DE33-0BA0 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
|
A |
26 |
32 |
38 |
38 |
45 |
60 |
|
A |
26 |
32 |
38 |
38 |
45 |
60 |
|
A |
18 |
26 |
32 |
32 |
38 |
45 |
|
A |
39 |
52 |
64 |
48 |
57 |
67 |
Rated power |
|
|
|
|
|
|
|
|
kW |
11 |
15 |
18.5 |
18.5 |
22 |
30 |
|
kW |
7.5 |
11 |
15 |
15 |
18.5 |
22 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
97 |
97 |
98 |
97 |
97 |
97 |
Power loss 4) at rated current |
kW |
0.299 |
0.365 |
0.435 |
0.478 |
0.569 |
0.784 |
Cooling air requirement |
m3/s (ft3/s) |
0.02 (0.7) |
0.02 (0.7) |
0.02 (0.7) |
0.039 (1.4) |
0.039 (1.4) |
0.039 (1.4) |
Sound pressure level LpA (1 m) |
dB |
66.1 |
66.1 |
66.1 |
56 |
56 |
56 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
1 |
Input current 5) |
|
|
|
|
|
|
|
|
A |
27 |
33 |
39 |
39 |
42 |
56 |
|
A |
19 |
27 |
33 |
33 |
36 |
42 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
M6 screw studs |
M6 screw studs |
M6 screw studs |
|
mm2 |
6 ... 16 |
10 ... 16 |
10 ... 16 |
16 ... 35 |
16 ... 35 |
16 ... 35 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
M6 screw studs |
M6 screw studs |
M6 screw studs |
|
mm2 |
6 ... 16 |
10 ... 16 |
10 ... 16 |
16 ... 35 |
16 ... 35 |
16 ... 35 |
Motor cable length, max. 6) |
|
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection 7) |
|
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55/UL Type 12 |
IP55 |
IP55 |
IP55 |
Dimensions |
|
|
|
|
|
|
|
|
mm (in) |
230 (9.06) |
230 (9.06) |
230 (9.06) |
320 (12.60) |
320 (12.60) |
320 (12.60) |
|
mm (in) |
620 (24.41) |
620 (24.41) |
620 (24.41) |
640 (25.20) |
640 (25.20) |
640 (25.20) |
|
|
|
|
|
|
|
|
|
mm (in) |
249 (9.80) |
249 (9.80) |
249 (9.80) |
329 (12.95) |
329 (12.95) |
329 (12.95) |
|
mm (in) |
266 (10.47) |
266 (10.47) |
266 (10.47) |
346 (13.62) |
346 (13.62) |
346 (13.62) |
Frame size |
|
FSC |
FSC |
FSC |
FSD |
FSD |
FSD |
Weight, approx. |
kg (lb) |
9.5 (20.95) |
9.5 (20.95) |
9.5 (20.95) |
31 (68.36) |
31 (68.36) |
31 (68.36) |
1) UL Type 12 only for frame size FSC
2) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
3) The base-load current IH is based on the duty cycle for high overload (HO).
4) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
5) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
6) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.
7) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55/UL Type 12. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules, degree of protection IP55 |
|||||
---|---|---|---|---|---|---|
With integrated line filter class A |
6SL3223-0DE33-7AA0 |
6SL3223-0DE34-5AA0 |
6SL3223-0DE35-5AA0 |
6SL3223-0DE37-5AA0 |
6SL3223-0DE38-8AA0 |
|
With integrated line filter class B |
6SL3223-0DE33-7BA0 |
6SL3223-0DE34-5BA0 |
6SL3223-0DE35-5BA0 |
6SL3223-0DE37-5BA0 |
6SL3223-0DE38-8BA0 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
75 |
90 |
110 |
145 |
178 |
|
A |
75 |
90 |
110 |
145 |
178 |
|
A |
60 |
75 |
90 |
110 |
145 |
|
A |
90 |
112 |
135 |
165 |
217 |
Rated power |
|
|
|
|
|
|
|
kW |
37 |
45 |
55 |
75 |
90 |
|
kW |
30 |
37 |
45 |
55 |
75 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
97 |
97 |
97 |
97 |
97 |
Power loss 3) at rated current |
kW |
0.855 |
1.073 |
1.122 |
1.542 |
1.98 |
Cooling air requirement |
m3/s (ft3/s) |
0.039 (1.4) |
0.039 (1.4) |
0.117 (4.1) |
0.117 (4.1) |
0.117 (4.1) |
Sound pressure level LpA (1 m) |
dB |
56 |
56 |
61 |
61 |
61 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
|
A |
70 |
84 |
102 |
135 |
166 |
|
A |
56 |
70 |
84 |
102 |
135 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
M6 screw studs |
M6 screw studs |
M8 screw studs |
M8 screw studs |
M8 screw studs |
|
mm2 |
25 ... 50 |
25 ... 50 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Motor connection U2, V2, W2 |
|
M6 screw studs |
M6 screw studs |
M8 screw studs |
M8 screw studs |
M8 screw studs |
|
mm2 |
25 ... 50 |
25 ... 50 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Motor cable length, max. 5) |
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection 6) |
|
IP55 |
IP55 |
IP55 |
IP55 |
IP55 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
320 (12.60) |
320 (12.60) |
410 (16.14) |
410 (16.14) |
410 (16.14) |
|
mm (in) |
751 (29.57) |
751 (29.57) |
915 (36.02) |
915 (36.02) |
915 (36.02) |
|
|
|
|
|
|
|
|
mm (in) |
329 (12.95) |
329 (12.95) |
416 (16.38) |
416 (16.38) |
416 (16.38) |
|
mm (in) |
346 (13.62) |
346 (13.62) |
433 (17.05) |
433 (17.05) |
433 (17.05) |
Frame size |
|
FSE |
FSE |
FSF |
FSF |
FSF |
Weight, approx. |
kg (lb) |
37 (81.6) (with filter cl. A) |
37 (81.6) (with filter cl. A) |
70 (154) |
70 (154) |
70 (154) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values of EN 61800‑3 Category C2 (filter A) or C1 table 14 (filter B). With unshielded cables, Categories C2 and C1 are not achieved.
6) It is essential to plug on an operator panel or the blanking cover in order to achieve degree of protection IP54/IP55. For more information, see Operator panels and blanking cover for PM230 Power Modules in section Supplementary system components.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules degree of protection IP20 Standard variant |
|||||
---|---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1NE11-3UG1 |
6SL3210-1NE11-7UG1 |
6SL3210-1NE12-2UG1 |
6SL3210-1NE13-1UG1 |
6SL3210-1NE14-1UG1 |
|
With integrated line filter class A |
6SL3210-1NE11-3AG1 |
6SL3210-1NE11-7AG1 |
6SL3210-1NE12-2AG1 |
6SL3210-1NE13-1AG1 |
6SL3210-1NE14-1AG1 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
1.3 |
1.7 |
2.2 |
3.1 |
4.1 |
|
A |
1.3 |
1.7 |
2.2 |
3.1 |
4.1 |
|
A |
0.9 |
1.3 |
1.7 |
2.2 |
3.1 |
|
A |
2 |
2.6 |
3.4 |
4.7 |
6.2 |
Rated power |
|
|
|
|
|
|
|
kW |
0.37 |
0.55 |
0.75 |
1.1 |
1.5 |
|
kW |
0.25 |
0.37 |
0.55 |
0.75 |
1.1 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
89 |
93 |
93 |
94 |
95 |
Power loss 3) at rated current |
kW |
0.031 |
0.034 |
0.041 |
0.049 |
0.06 |
Cooling air requirement |
m3/s (ft3/s) |
0.002 (0.1) |
0.002 (0.1) |
0.005 (0.2) |
0.005 (0.2) |
0.005 (0.2) |
Sound pressure level LpA (1 m) |
dB |
<50 |
<50 |
<50 |
<50 |
<50 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
|
A |
1.3 |
1.8 |
2.3 |
3.2 |
4.2 |
|
A |
0.9 |
1.3 |
1.8 |
2.3 |
3.2 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
1 ... 2.5 |
Motor cable length, max. 5) |
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
73 (2.87) |
73 (2.87) |
73 (2.87) |
73 (2.87) |
73 (2.87) |
|
mm (in) |
196 (7.72) |
196 (7.72) |
196 (7.72) |
196 (7.72) |
196 (7.72) |
|
|
|
|
|
|
|
|
mm (in) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
|
mm (in) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
Frame size |
|
FSA |
FSA |
FSA |
FSA |
FSA |
Weight, approx. |
|
|
|
|
|
|
|
kg (lb) |
1.4 (3.09) |
1.4 (3.09) |
1.4 (3.09) |
1.4 (3.09) |
1.4 (3.09) |
|
kg (lb) |
1.6 (3.53) |
1.6 (3.53) |
1.6 (3.53) |
1.6 (3.53) |
1.6 (3.53) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules degree of protection IP20 Standard variant |
|||||
---|---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1NE15-8UG1 |
6SL3210-1NE17-7UG1 |
6SL3210-1NE21-0UG1 |
6SL3210-1NE21-3UG1 |
6SL3210-1NE21-8UG1 |
|
With integrated line filter class A |
6SL3210-1NE15-8AG1 |
6SL3210-1NE17-7AG1 |
6SL3210-1NE21-0AG1 |
6SL3210-1NE21-3AG1 |
6SL3210-1NE21-8AG1 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
5.9 |
7.7 |
10.2 |
13.2 |
18 |
|
A |
5.9 |
7.7 |
10.2 |
13.2 |
18 |
|
A |
4.1 |
5.9 |
7.7 |
10.2 |
13.2 |
|
A |
8.9 |
11.8 |
15.4 |
20.4 |
27 |
Rated power |
|
|
|
|
|
|
|
kW |
2.2 |
3 |
4 |
5.5 |
7.5 |
|
kW |
1.5 |
2.2 |
3 |
4 |
5.5 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
96 |
96 |
97 |
97 |
97 |
Power loss 3) at rated current |
kW |
0.078 |
0.102 |
0.13 |
0.165 |
0.224 |
Cooling air requirement |
m3/s (ft3/s) |
0.005 (0.2) |
0.005 (0.2) |
0.009 (0.3) |
0.009 (0.3) |
0.009 (0.3) |
Sound pressure level LpA (1 m) |
dB |
<50 |
<50 |
<62 |
<62 |
<62 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
|
A |
6.1 |
8 |
11 |
14 |
19 |
|
A |
4.2 |
6.1 |
8 |
11 |
14 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1.5 ... 2.5 |
1.5 ... 2.5 |
1.5 ... 6 |
1.5 ... 6 |
1.5 ... 6 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1.5 ... 2.5 |
1.5 ... 2.5 |
1.5 ... 6 |
1.5 ... 6 |
1.5 ... 6 |
Motor cable length, max. 5) |
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
73 (2.87) |
73 (2.87) |
100 (328.10) |
100 (328.10) |
100 (328.10) |
|
mm (in) |
196 (7.72) |
196 (7.72) |
292 (11.50) |
292 (11.50) |
292 (11.50) |
|
|
|
|
|
|
|
|
mm (in) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
|
mm (in) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
Frame size |
|
FSA |
FSA |
FSB |
FSB |
FSB |
Weight, approx. |
|
|
|
|
|
|
|
kg (lb) |
1.4 (3.09) |
1.4 (3.09) |
2.8 (6.17) |
2.8 (6.17) |
2.8 (6.17) |
|
kg (lb) |
1.6 (3.53) |
1.6 (3.53) |
3 (6.61) |
3 (6.61) |
3 (6.61) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules degree of protection IP20 Standard variant |
|||||
---|---|---|---|---|---|---|
Without integrated line filter |
6SL3210- |
6SL3210- |
6SL3210- |
6SL3210- |
6SL3210- |
|
With integrated line filter class A |
6SL3210- |
6SL3210- |
6SL3210- |
6SL3210- |
6SL3210- |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
26 |
32 |
38 |
45 |
60 |
|
A |
26 |
32 |
38 |
45 |
60 |
|
A |
18 |
26 |
32 |
38 |
45 |
|
A |
39 |
52 |
64 |
57 |
67 |
Rated power |
|
|
|
|
|
|
|
kW |
11 |
15 |
18.5 |
22 |
30 |
|
kW |
7.5 |
11 |
15 |
18.5 |
22 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
97 |
97 |
98 |
98 |
97 |
Power loss 3) at rated current |
kW |
0.291 |
0.355 |
0.423 |
0.539 |
0.726 |
Cooling air requirement |
m3/s (ft3/s) |
0.019 (0.7) |
0.019 (0.7) |
0.019 (0.7) |
0.08 (2.8) |
0.08 (2.8) |
Sound pressure level LpA (1 m) |
dB |
<65 |
<65 |
<65 |
<60 |
<60 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
|
A |
27 |
33 |
39 |
42 |
56 |
|
A |
19 |
27 |
33 |
36 |
42 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
M6 screw studs |
M6 screw studs |
|
mm2 |
6 ... 16 |
6 ... 16 |
6 ... 16 |
16 ... 35 |
16 ... 35 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
M6 screw studs |
M6 screw studs |
|
mm2 |
6 ... 16 |
6 ... 16 |
6 ... 16 |
16 ... 35 |
16 ... 35 |
Motor cable length, max. 5) |
|
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
140 (5.51) |
140 (5.51) |
140 (5.51) |
275 (10.83) |
275 (10.83) |
|
|
|
|
|
|
|
|
mm (in) |
355 (13.98) |
355 (13.98) |
355 (13.98) |
419 (16.50) |
419 (16.50) |
|
mm (in) |
355 (13.98) |
355 (13.98) |
355 (13.98) |
512 (20.16) |
512 (20.16) |
|
|
|
|
|
|
|
|
mm (in) |
165 (6.50) |
165 (6.50) |
165 (6.50) |
204 (8.03) |
204 (8.03) |
|
mm (in) |
245 (9.65) |
245 (9.65) |
245 (9.65) |
275 (10.83) |
275 (10.83) |
Frame size |
|
FSC |
FSC |
FSC |
FSD |
FSD |
Weight, approx. |
|
|
|
|
|
|
|
kg (lb) |
4.5 (9.92) |
4.5 (9.92) |
4.5 (9.92) |
11 (24.3) |
11 (24.3) |
|
kg (lb) |
5.1 (11.25) |
5.1 (11.25) |
5.1 (11.25) |
14 (30.87) |
14 (30.87) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules degree of protection IP20 Standard variant |
||||
---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1NE27-5UL0 |
6SL3210-1NE28-8UL0 |
6SL3210-1NE31-1UL0 |
6SL3210-1NE31-5UL0 |
|
With integrated line filter class A |
6SL3210-1NE27-5AL0 |
6SL3210-1NE28-8AL0 |
6SL3210-1NE31-1AL0 |
6SL3210-1NE31-5AL0 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
A |
75 |
90 |
110 |
145 |
|
A |
75 |
90 |
110 |
145 |
|
A |
60 |
75 |
90 |
110 |
|
A |
90 |
112 |
135 |
165 |
Rated power |
|
|
|
|
|
|
kW |
37 |
45 |
55 |
75 |
|
kW |
30 |
37 |
45 |
55 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
Efficiency η |
% |
97 |
97 |
97 |
97 |
Power loss 3) at rated current |
kW |
0.791 |
0.976 |
1.237 |
1.69 |
Cooling air requirement |
m3/s (ft3/s) |
0.08 (2.8) |
0.08 (2.8) |
0.15 (5.3) |
0.15 (5.3) |
Sound pressure level LpA (1 m) |
dB |
<60 |
<60 |
<60 |
<60 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
|
A |
70 |
84 |
102 |
135 |
|
A |
56 |
70 |
84 |
102 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
M6 screw studs |
M6 screw studs |
M8 screw studs |
M8 screw studs |
|
mm2 |
25 ... 50 |
25 ... 50 |
35 ... 120 |
35 ... 120 |
Motor connection U2, V2, W2 |
|
M6 screw studs |
M6 screw studs |
M8 screw studs |
M8 screw studs |
|
mm2 |
25 ... 50 |
25 ... 50 |
35 ... 120 |
35 ... 120 |
Motor cable length, max. 5) |
|
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
mm (in) |
275 (10.83) |
275 (10.83) |
350 (13.78) |
350 (13.78) |
|
|
|
|
|
|
|
mm (in) |
499 (19.65) |
499 (19.65) |
634 (24.96) |
634 (24.96) |
|
mm (in) |
635 (25) |
635 (25) |
934 (36.77) |
934 (36.77) |
|
|
|
|
|
|
|
mm (in) |
204 (8.03) |
204 (8.03) |
316 (12.44) |
316 (12.44) |
|
mm (in) |
275 (10.83) |
275 (10.83) |
387 (15.24) |
387 (15.24) |
Frame size |
|
FSE |
FSE |
FSF |
FSF |
Weight, approx. |
|
|
|
|
|
|
kg (lb) |
15 (33.1) |
15 (33.1) |
34 (74.97) |
34 (74.97) |
|
kg (lb) |
22 (48.5) |
22 (48.5) |
46 (101.43) |
46 (101.43) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.
Line voltage 380 ... 480 V 3 AC |
PM230 Power Modules degree of protection IP20 Push Through variant |
|||
---|---|---|---|---|
Without integrated line filter |
6SL3211-1NE17-7UG1 |
6SL3211-1NE21-8UG1 |
6SL3211-1NE23-8UG1 |
|
With integrated line filter class A |
6SL3211-1NE17-7AG1 |
6SL3211-1NE21-8AG1 |
6SL3211-1NE23-8AG1 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
A |
7.7 |
18 |
38 |
|
A |
7.7 |
18 |
38 |
|
A |
5.9 |
13.2 |
32 |
|
A |
11.8 |
27 |
64 |
Rated power |
|
|
|
|
|
kW |
3 |
7.5 |
18.5 |
|
kW |
2.2 |
5.5 |
15 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
Efficiency η |
% |
96 |
97 |
98 |
Power loss 3) at rated current |
kW |
0.102 |
0.224 |
0.423 |
Cooling air requirement |
m3/s (ft3/s) |
0.005 (0.2) |
0.009 (0.3) |
0.019 (0.7) |
Sound pressure level LpA (1 m) |
dB |
<56 |
<62 |
<65 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
Input current 4) |
|
|
|
|
|
A |
8 |
19 |
39 |
|
A |
6.1 |
14 |
33 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1.5 ... 2.5 |
4 ... 6 |
6 ... 16 |
Motor connection U2, V2, W2 |
|
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
Screw-type terminals, plug-in |
|
mm2 |
1 ... 2.5 |
4 ... 6 |
10 ... 16 |
Motor cable length, max. 5) |
|
|
|
|
|
m (ft) |
25 (82) |
25 (82) |
25 (82) |
|
m (ft) |
100 (328) |
100 (328) |
100 (328) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
mm (in) |
126 (4.96) |
154 (6.06) |
200 (7.87) |
|
mm (in) |
238 (9.37) |
345 (13.58) |
411 (16.18) |
|
|
|
|
|
|
mm (in) |
171 (6.73) |
171 (6.73) |
171 (6.73) |
|
mm (in) |
251 (9.88) |
251 (9.88) |
251 (9.88) |
Frame size |
|
FSA |
FSB |
FSC |
Weight, approx. With integrated line filter |
|
|
|
|
|
kg (lb) |
1.7 (3.75) |
3.4 (7.50) |
5.4 (11.91) |
|
kg (lb) |
1.9 (4.19) |
3.6 (7.94) |
6 (13.23) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Typical values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.
5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800‑3 Category C2. With unshielded cables, Category C2 is not achieved.
Pulse frequency
Rated power 1) |
Rated output current in A for a pulse frequency of |
|||||||
---|---|---|---|---|---|---|---|---|
400 V |
460 V |
|||||||
kW |
hp |
4 kHz |
6 kHz |
8 kHz |
10 kHz |
12 kHz |
14 kHz |
16 kHz |
0.37 |
0.5 |
1.3 |
1.11 |
0.91 |
0.78 |
0.65 |
0.59 |
0.52 |
0.55 |
0.5 |
1.7 |
1.45 |
1.19 |
1.02 |
0.85 |
0.77 |
0.68 |
0.75 |
0.75 |
2.2 |
1.87 |
1.54 |
1.32 |
1.1 |
0.99 |
0.88 |
1.1 |
1 |
3.1 |
2.64 |
2.17 |
1.86 |
1.55 |
1.4 |
1.24 |
1.5 |
2 |
4.1 |
3.49 |
2.87 |
2.46 |
2.05 |
1.85 |
1.64 |
2.2 |
3 |
5.9 |
5.02 |
4.13 |
3.54 |
2.95 |
2.66 |
2.36 |
3 |
3 |
7.7 |
6.55 |
5.39 |
4.62 |
3.85 |
3.47 |
3.08 |
4 |
5 |
10.2 |
8.67 |
7.14 |
6.12 |
5.1 |
4.59 |
4.08 |
5.5 |
7.5 |
13.2 |
11.22 |
9.24 |
7.92 |
6.6 |
5.94 |
5.28 |
7.5 |
10 |
18 |
15.3 |
12.6 |
10.8 |
9 |
8.1 |
7.2 |
11 |
15 |
26 |
22.1 |
18.2 |
15.6 |
13 |
11.7 |
10.4 |
15 |
15 |
32 |
27.2 |
22.4 |
19.2 |
16 |
14.4 |
12.8 |
18.5 |
20 |
38 |
32.3 |
26.6 |
22.8 |
19 |
17.1 |
15.2 |
22 |
25 |
45 |
38.25 |
31.5 |
27 |
22.5 |
20.25 |
18 |
30 |
30 |
60 |
51 |
42 |
36 |
30 |
27 |
24 |
37 |
40 |
75 |
63.75 |
52.5 |
45 |
37.5 |
33.75 |
30 |
45 |
50 |
90 |
76.5 |
63 |
54 |
45 |
40.5 |
36 |
55 |
60 |
110 |
93.5 |
77 |
66 2) |
55 2) |
49.5 2) |
44 2) |
75 |
75 |
145 |
123.3 |
101.5 |
– |
– |
– |
– |
90 |
100 |
178 |
151.3 |
124.6 |
– |
– |
– |
– |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO).
2) Values apply only to IP20 variants.
Ambient temperature
Permissible output current as a function of the ambient temperature for low overload (LO) for PM230 Power Modules, frame sizes FSA to FSC
Permissible output current as a function of ambient temperature for low overload (LO) for PM230 Power Modules, frame sizes FSD to FSF
Permissible output current as a function of ambient temperature for high overload (HO) PM230 Power Modules, frame sizes FSA to FSC
Permissible output current as a function of ambient temperature for high overload (HO) PM230 Power Modules, frame sizes FSD to FSF
Note:
The operating temperature ranges of the Control Units should be taken into account. The temperature ranges are specified in the section Technical specifications under Control Units.
Installation altitude
Permissible line supplies as a function of the installation altitude
Note:
The connected motors, power elements and components must be considered separately.
Permissible output current as a function of the installation altitude for PM230 Power Modules, frame sizes FSA to FSF
System operating voltage
Permissible output current as a function of the line voltage for PM230 Power Modules, frame sizes FSA to FSF
Permissible rated power as a function of the line voltage for PM230 Power Modules, frame sizes FSA to FSF
Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP55, with integrated line filter class A/B
Frame size |
Dimensions in mm (inches) |
Drilling dimensions in mm (inches) |
Cooling clearance in mm (inches) |
Mounting |
||||||
---|---|---|---|---|---|---|---|---|---|---|
|
a |
b |
c |
d |
e |
f |
top |
bottom |
side |
With bolts, nuts and washers |
PM230 Power Modules, degree of protection IP55 with integrated line filter class A/B |
||||||||||
FSA |
154 |
460 |
249 |
132 |
445 |
11 |
100 |
0 |
0 |
4 × M4 |
FSB |
180 |
540 |
249 |
158 |
524 |
11 |
100 |
0 |
0 |
4 × M4 |
FSC |
230 |
620 |
249 |
208 |
604 |
11 |
125 |
0 |
0 |
4 × M5 |
FSD |
320 |
640 |
329 |
285 |
600 |
17.5 |
300 |
0 |
50 |
4 × M8 |
FSE |
320 |
751 |
329 |
285 |
710 |
17.5 |
300 |
0 |
50 |
4 × M8 |
FSF |
410 |
915 |
416 |
370 |
870 |
20 |
350 |
0 |
50 |
4 × M8 |
1) Increased depth:
• When the IOP is plugged on, the depth increases by 17 mm (0.67 in)
• When the BOP‑2/blanking cover is plugged on, the depth increases by 7 mm (0.28 in)
2) Up to 40 °C (104 °F) without any lateral clearance.
Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, Standard variant, with/without integrated line filter class A
Frame size |
Dimensions in mm (inches) |
Drilling dimensions in mm (inches) |
Cooling clearance in mm (inches) |
Mounting |
||||||
---|---|---|---|---|---|---|---|---|---|---|
|
a |
b |
c |
d |
e |
f |
top |
bottom |
side 2) |
With bolts |
PM230 Power Modules, degree of protection IP20, Standard variant, with/without integrated line filter class A |
||||||||||
FSA |
73 |
196 |
165 |
62.3 |
186 |
6 |
80 |
100 |
0 |
3 × M4 |
FSB |
100 |
292 |
165 |
80 |
281 |
6 |
80 |
100 |
0 |
4 × M4 |
FSC |
140 |
355 |
165 |
120 |
343 |
6 |
80 |
100 |
0 |
4 × M5 |
FSD |
275 |
419/512 |
204 |
235 |
325/419 |
11 |
300 |
300 |
0 |
4 x M6 |
FSE |
275 |
499/635 |
204 |
235 |
405/541 |
11 |
300 |
300 |
0 |
4 x M6 |
FSF |
350 |
634/934 |
316 |
300 |
598/899 |
11 |
350 |
350 |
0 |
4 × M8 |
1) Increased depth:
• When the CU230P-2 Control Unit is plugged on, the depth increases by 58 mm (2.28 in) for FSA to FSC and by 49 mm (1.93 in) for FSD to FSF
• When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)
• When the BOP‑2 is plugged on, the depth increases by a further 12 mm (0.47 in)
2)The Power Modules can be mounted side by side. A side clearance of 1 mm (0.04 in) is recommended for tolerance-related reasons.
Principle dimension drawing and drill pattern for PM230 Power Modules, degree of protection IP20, Push Through variant, with/without integrated line filter class A
Frame size |
Dimensions in mm (inches) |
Drilling dimensions in mm (inches) |
Section of cabinet in mm (inches) |
Cooling clearance in mm (inches) |
Mounting |
|||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
|
a |
b |
c |
d |
e |
f |
g |
h |
top |
bottom |
side 2) |
With bolts |
PM230 Power Modules, degree of protection IP20, Push Through variant, with/without integrated line filter class A |
||||||||||||
FSA |
125.9 |
238 |
171 |
106 |
103 |
27 |
88 |
198 |
80 |
100 |
0 |
M5 |
FSB |
153.9 |
345 |
171 |
134 |
147.5 |
34.5 |
116 |
304 |
80 |
100 |
0 |
M5 |
FSC |
200 |
410.5 |
171 |
174 |
123 |
30.5 |
156 |
365 |
80 |
100 |
0 |
M5 |
1) Overall depth, of which 117.7 mm (4.63 in) is inside and 53.1 mm (2.09 in) is outside the control cabinet.
Increased depth:
• When the CU230P‑2 Control Unit is plugged on, the depth increases by 58 mm (2.28 in)
• When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)
• When the BOP‑2 is plugged on, the depth increases by a further 12 mm (0.47 in)
2)The Power Modules can be mounted side by side (mounting frame to mounting frame). A side clearance of 1 mm (0.04 in) is recommended for tolerance-related reasons.
(Nguyễn Thảo Trường - http://DienElectric.com theo Siemens)