Whether installed in the intake and exhaust fans of air-conditioning systems, in pumps for heating and cooling circuits, or in compressors for refrigeration units: SINAMICS G120P converters are ideally suited to meet every requirement of building management systems.
Stay flexible: Due to their IP20 and IP55 degrees of protection, the PM230 Power Modules can not only be installed in the control cabinet, but can also be directly at the machine. And thanks to different EMC filters, they can be used both in the public power grid and in industrial networks.
A well-thought-out portfolio: Apart from standard functions such as setpoint specifications, on/off switching logic, protection and monitoring of machine, motor and converter, SINAMICS G120P also offers numerous industry-specific functions. These include the regulation of two or multiple zones and one fire protection mode which ensures the longest possible operation in an emergency.
- Full control – Real-time clock with exact time stamp for error and warning logging, max. buffer time five days, automatic summer / winter changeover
- Freely programmable – Digital timers for the control of three selectable events depending on the weekday / hour / minute
SINAMICS G120P in the Building Technologies: |
|
---|---|
Power: |
0,37 - 90 kW |
Voltage: |
3 AC 380 - 480 V |
Control procedure: |
U/f control with stator flux orientation, vector control without encoder |
Growing complexity of plants and globalization of markets: The drives of the SINAMICS G120P series always have the right answer for the special features of the process industry.
Usable and available worldwide – SINAMICS G120P is ready to meet your global requirements. And with the key functions of speed control, controlling range, efficiency and communication level, it ensures simple operation.
Thanks to the upgraded PM330 Power Modules, you now have a complete series of SINAMICS G120P products at your disposal: in all sizes and across all voltage ranges, from 400 V to 690 V. A flexibly applicable and consistent approach, which minimizes your configuration and implementation overheads.
The new PM240P-2 Power Modules increases your process reliability: with integrated safety functionality up to the SIL3 level.
- Process reliability – Utmost safety level thanks to Integrated safety functions, safe electronic switch-off (Safe Torque-off / Safe Stop 1)
- Robustness – Even for special operating conditions such as temperatures ranging from -10° C to 60° C and aggressive environments (resistance to pollutants)
- Cost saving – Increased energy efficiency with higher output voltage (98 %) through integrated dc link reactor
- Enhanced flexibility – due to the new voltage level up to 690 V
- Saving space – allows compact control cabinets
- Robustness – through numerous functions such as output voltage sensing
- Total integration – the complete product series is available
SINAMICS G120P in the Process industry |
|
---|---|
Power: |
11 - 630 kW |
Voltage: |
3 AC 380 - 480 V and 3 AC 500 - 690 V |
Control procedure: |
U/f control with stator flux orientation, vector control without encoder |
Power Modules for industrial applications and building technology
Control Units have been especially designed for pump, fan, compressor applications
Supplementary system components for SINAMICS G120P
The new PM240P‑2 Power Modules are based on a new hardware platform. This permits a higher power density to be achieved. PM240P-2 Power Modules do not have an integrated braking chopper.
In addition, PM240P-2 Power Modules are also suitable for use in safety-related applications. In conjunction with an external tripping unit (e.g. SIRIUS 3SK1), the drive becomes a Safety Integrated Drive with the Safe Torque Off (STO) safety function with a maximum Safety Integrity Level of SIL 3.
PM240P-2 Power Modules, frame sizes FSD to FSF, are available both with and without an integrated line filter class A in a compact design for line voltages of 380 V to 480 V 3 AC and 500 V to 690 V 3 AC. PM240P‑2 Power Modules with integrated line filter class A are suitable for connection to TN supply systems. Power Modules without an integrated line filter can be connected to grounded TN/TT systems and non-grounded IT systems.
The permissible cable lengths between inverter and motor are limited (for max. permissible cable lengths, see section Integration). Longer cables can be used if output reactors are connected (see section Load-side power components).
Note:
Shield plates and shield connection kits are available. These can be used in the wiring installation for the Control Units and Power Modules to ensure that it complies with EMC guidelines.
For more information, see Shield connection kits and shield plates for Control Units and Power Modules in section Supplementary system components.
All PM240P-2 Power Modules have the following connections and interfaces:
Connection diagram for PM240P-2 Power Module with or without integrated line filter class A
The following load-side power components are optionally available in the appropriate frames sizes for the Power Modules:
PM240P-2 Power Module |
System operating voltage |
Frame size |
||
---|---|---|---|---|
FSD |
FSE |
FSF |
||
Output reactor |
380 ... 480 V 3 AC 500 ... 690 V 3 AC |
✓ – |
✓ – |
✓ ✓ |
dv/dt filter plus VPL |
500 ... 690 V 3 AC |
✓ |
✓ |
✓ |
The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result in the following maximum cable lengths:
PM240P-2 Power Module, frame sizes FSD and FSE |
System operating voltage |
Maximum permissible motor cable lengths (shielded/unshielded) in m (ft) |
---|---|---|
Without output option |
380 ... 480 V 3 AC |
200/300 (656/984) |
Without output option, compliance with Category C2 acc. to EN 61800-3 |
380 ... 480 V 3 AC |
150/- (492/-) |
With two output reactors in series |
380 ... 480 V 3 AC |
350/525 (1148/1722) |
With dv/dt filter plus VPL |
500 ... 690 V 3 AC |
300/450 (984/1476) |
PM240P-2 Power Module, frame size FSF |
System operating voltage |
Maximum permissible motor cable lengths (shielded/unshielded) in m (ft) |
---|---|---|
Without output option |
380 ... 480 V 3 AC 500 ... 690 V 3 AC |
300/450 (984/1476) 300/450 (984/1476) |
Without output option, compliance with Categories C2 and/or C3 acc. to EN 61800-3 |
380 ... 480 V 3 AC 500 ... 690 V 3 AC |
150/- (Category C2) 150/- (Category C3) |
With two output reactors in series |
380 ... 480 V 3 AC 500 ... 690 V 3 AC |
525/800 (1722/2625) 525/800 (1722/2625) |
With dv/dt filter plus VPL |
500 ... 690 V 3 AC |
300/450 (984/1476) |
Power Modules |
PM240P-2 |
---|---|
System operating voltage |
380 ... 480 V 3 AC ±10 % (in operation -20 % < 1 min) 500 ... 690 V 3 AC ±10 % (in operation -20 % < 1 min) |
Grid requirement |
>25 |
Input frequency |
47 ... 63 Hz |
Output frequency |
|
|
0 ... 550 Hz |
|
0 ... 200 Hz |
Pulse frequency |
|
|
up to 90 kW (121 hp) (LO): 4 kHz from 110 kW (148 hp) (LO): 2 kHz Higher pulse frequencies up to 16 kHz, see derating data |
|
2 kHz, can be adjusted to 4 kHz |
Power factor λ |
0.95 at 380 ... 480 V 3 AC 0.9 at 500 ... 690 V 3 AC |
Offset factor cos φ |
0.99 |
Inverter efficiency |
>97 % at 380 ... 480 V 3 AC >98 % at 500 ... 690 V 3 AC |
Output voltage, max. In % of input voltage |
95 % |
Overload capability |
|
Note: When the overload capability is used, the base-load current IL is not reduced. |
1.35 × base-load current IL (i.e. 135 % overload) for 3 s plus 1.1 × base-load current IL (i.e. 110 % overload) for 57 s within a cycle time of 300 s |
Note: When the overload capability is used, the base-load current IH is not reduced. |
1.5 × base-load current IH (i. e. 150 % overload) for 60 s within a cycle time of 300 s |
Electromagnetic compatibility |
|
Possible braking methods |
|
Degree of protection |
IP20 |
Operating temperature |
|
|
-20 ... +40 °C (-4 ... +104 °F) without derating |
|
-20 ... +50 °C (-4 ... +122 °F) without derating |
Relative humidity |
5 … 95 %, condensation not permitted |
Storage temperature |
-25 ... +55 °C (-13 ... +131 °F) |
Cooling |
Internal air cooling, power units with increased air cooling by built-in fans |
Installation altitude |
Up to 1000 m (3281 ft) above sea level without derating, |
Protection functions |
|
Short-Circuit Current Rating SCCR (Short-Circuit Current Rating) 1) |
65 kA |
Compliance with standards |
UL, cUL, CE, RCM, SEMI F47 |
CE marking |
According to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU |
1) Applies to industrial control panel installations to NEC article 409 or UL 61800-5-1.
Line voltage 380 ... 480 V 3 AC |
PM240P-2 Power Modules |
|||||
---|---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1RE24-5UL0 |
6SL3210-1RE26-0UL0 |
6SL3210-1RE27-5UL0 |
6SL3210-1RE28-8UL0 |
6SL3210-1RE31-1UL0 |
|
With integrated line filter |
6SL3210-1RE24-5AL0 |
6SL3210-1RE26-0AL0 |
6SL3210-1RE27-5AL0 |
6SL3210-1RE28-8AL0 |
6SL3210-1RE31-1AL0 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
|
A |
45 |
60 |
75 |
90 |
110 |
|
A |
45 |
60 |
75 |
90 |
110 |
|
A |
38 |
45 |
60 |
75 |
90 |
|
A |
61 |
81 |
102 |
122 |
149 |
Rated power |
|
|
|
|
|
|
|
kW |
22 |
30 |
37 |
45 |
55 |
|
kW |
18.5 |
22 |
30 |
37 |
45 |
Rated pulse frequency |
kHz |
4 |
4 |
4 |
4 |
4 |
Efficiency η |
% |
98 |
98 |
98 |
98 |
98 |
Power loss 3) at rated current |
|
|
|
|
|
|
|
kW |
0.7 |
0.85 |
1.12 |
1.25 |
1.59 |
|
kW |
0.71 |
0.85 |
1.12 |
1.28 |
1.63 |
Cooling air requirement |
m3/s (ft3/s) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.083 (2.93) |
0.083 (2.93) |
Sound pressure level LpA (1 m) |
dB |
71.6 |
71.6 |
71.6 |
70.6 |
70.6 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
Rated input current Irated4) |
|
42 |
57 |
70 |
86 |
104 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
25 ... 70 |
25 ... 70 |
Motor connection U2, V2, W2 |
|
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
25 ... 70 |
25 ... 70 |
Feedback connection F3, R1 |
|
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
25 ... 70 |
25 ... 70 |
PE connection |
|
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
Screw terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
25 ... 70 |
25 ... 70 |
Motor cable length 5), max. |
|
|
|
|
|
|
|
m (ft) |
200 (656) |
200 (656) |
200 (656) |
200 (656) |
200 (656) |
|
m (ft) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
mm (in) |
200 (7.87) |
200 (7.87) |
200 (7.87) |
275 (10.8) |
275 (10.8) |
|
mm (in) |
472 (18.6) |
472 (18.6) |
472 (18.6) |
551 (21.7) |
551 (21.7) |
|
|
|
|
|
|
|
|
mm (in) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
|
mm (in) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
Frame size |
|
FSD |
FSD |
FSD |
FSE |
FSE |
Weight, approx. |
|
|
|
|
|
|
|
kg (lb) |
16.6 (36.6) |
18.3 (40.3) |
18.3 (40.3) |
26 (57.3) |
26 (57.3) |
|
kg (lb) |
18.3 (40.3) |
19 (41.9) |
19 (41.9) |
28 (61.7) |
28 (61.7) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Maximum values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance. The input currents apply for rated power loading (based on Irated) for a line impedance corresponding to uK = 1 %.
5) The specified cable lengths apply to Power Modules without output option and without compliance with the limit values for RI suppression.
Line voltage 380 ... 480 V 3 AC |
PM240P-2 Power Modules |
||||
---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1RE31-5UL0 |
6SL3210-1RE31-8UL0 |
6SL3210-1RE32-1UL0 |
6SL3210-1RE32-5UL0 |
|
With integrated line filter |
6SL3210-1RE31-5AL0 |
6SL3210-1RE31-8AL0 |
6SL3210-1RE32-1AL0 |
6SL3210-1RE32-5AL0 |
|
Output current at 50 Hz 400 V 3 AC |
|
|
|
|
|
|
A |
145 |
178 |
205 |
250 |
|
A |
145 |
178 |
205 |
250 |
|
A |
110 |
145 |
178 |
205 |
|
A |
196 |
214 |
277 |
338 |
Rated power |
|
|
|
|
|
|
kW |
75 |
90 |
110 |
132 |
|
kW |
55 |
75 |
90 |
110 |
Rated pulse frequency |
kHz |
4 |
4 |
2 |
2 |
Efficiency η |
% |
98 |
98 |
98 |
98 |
Power loss 3) at rated current |
|
|
|
|
|
|
kW |
1.58 |
2.07 |
2.28 |
2.97 |
|
kW |
1.6 |
2.1 |
2.31 |
3.01 |
Cooling air requirement |
m3/s (ft3/s) |
0.153 (5.40) |
0.153 (5.40) |
0.153 (5.40) |
0.153 (5.40) |
Sound pressure level LpA (1 m) |
dB |
67.7 |
67.7 |
67.7 |
67.7 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
Rated input current Irated4) |
A |
140 |
172 |
198 |
242 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Motor connection U2, V2, W2 |
|
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Feedback connection F3, R1 |
|
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
35 ... 2 x 120 |
35 ... 2 x 120 |
35 ... 2 x 120 |
35 ... 2 x 120 |
PE connection |
|
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Motor cable length 5), max. |
|
|
|
|
|
|
m (ft) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
|
m (ft) |
450 (1476) |
450 (1476) |
450 (1476) |
450 (1476) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
mm (in) |
305 (12.01) |
305 (12.01) |
305 (12.01) |
305 (12.01) |
|
mm (in) |
708 (27.9) |
708 (27.9) |
708 (27.9) |
708 (27.9) |
|
|
|
|
|
|
|
mm (in) |
357 (14.06) |
357 (14.06) |
357 (14.06) |
357 (14.06) |
|
mm (in) |
394.5 (15.5) |
394.5 (15.5) |
394.5 (15.5) |
394.5 (15.5) |
Frame size |
|
FSF |
FSF |
FSF |
FSF |
Weight, approx. |
|
|
|
|
|
|
kg (lb) |
57 (126) |
57 (126) |
61 (134) |
61 (134) |
|
kg (lb) |
63 (139) |
63 (139) |
63 (139) |
63 (139) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Maximum values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance. The input currents apply for rated power loading (based on Irated) for a line impedance corresponding to uK = 1 %.
5) The specified cable lengths apply to Power Modules without output option and without compliance with the limit values for RI suppression.
Line voltage 500 ... 690 V 3 AC |
PM240P-2 Power Modules |
||||||
---|---|---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1RH21-4UL0 |
6SL3210-1RH22-0UL0 |
6SL3210-1RH22-3UL0 |
6SL3210-1RH22-7UL0 |
6SL3210-1RH23-5UL0 |
6SL3210-1RH24-2UL0 |
|
With integrated line filter |
6SL3210-1RH21-4AL0 |
6SL3210-1RH22-0AL0 |
6SL3210-1RH22-3AL0 |
6SL3210-1RH22-7AL0 |
6SL3210-1RH23-5AL0 |
6SL3210-1RH24-2AL0 |
|
Output current at 50 Hz 690 V 3 AC |
|
|
|
|
|
|
|
|
A |
14 |
19 |
23 |
27 |
35 |
42 |
|
A |
14 |
19 |
23 |
27 |
35 |
42 |
|
A |
11 |
14 |
19 |
23 |
27 |
35 |
|
A |
19 |
26 |
32 |
37 |
48 |
57 |
Rated power |
|
|
|
|
|
|
|
|
kW |
11 |
15 |
18.5 |
22 |
30 |
37 |
|
kW |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
Rated pulse frequency |
kHz |
2 |
2 |
2 |
2 |
2 |
2 |
Efficiency η |
% |
98 |
98 |
98 |
98 |
98 |
98 |
Power loss 3) at rated current |
|
|
|
|
|
|
|
|
kW |
0.36 |
0.45 |
0.52 |
0.61 |
0.77 |
0.94 |
|
kW |
0.36 |
0.45 |
0.53 |
0.61 |
0.78 |
0.94 |
Cooling air requirement |
m3/s (ft3/s) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
Sound pressure level LpA (1 m) |
dB |
71.6 |
71.6 |
71.6 |
71.6 |
71.6 |
71.6 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
1 |
Rated input current Irated4) |
A |
14 |
18 |
22 |
25 |
33 |
40 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
Motor connection U2, V2, W2 |
|
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
Feedback connection F3, R1 |
|
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
PE connection |
|
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
Screw-type terminal |
|
mm2 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
10 ... 35 |
Motor cable length 5), max. |
|
|
|
|
|
|
|
|
m (ft) |
200 (656) |
200 (656) |
200 (656) |
200 (656) |
200 (656) |
200 (656) |
|
m (ft) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
|
mm (in) |
200 (7.87) |
200 (7.87) |
200 (7.87) |
200 (7.87) |
200 (7.87) |
200 (7.87) |
|
mm (in) |
472 (18.6) |
472 (18.6) |
472 (18.6) |
472 (18.6) |
472 (18.6) |
472 (18.6) |
|
|
|
|
|
|
|
|
|
mm (in) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
237 (9.33) |
|
mm (in) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
274.5 (10.8) |
Frame size |
|
FSD |
FSD |
FSD |
FSD |
FSD |
FSD |
Weight, approx. |
|
|
|
|
|
|
|
|
kg (lb) |
17.4 (38.4) |
17.4 (38.4) |
17.4 (38.4) |
17.4 (38.4) |
17.4 (38.4) |
17.4 (38.4) |
|
kg (lb) |
18.9 (41.7) |
18.9 (41.7) |
18.9 (41.7) |
18.9 (41.7) |
18.9 (41.7) |
18.9 (41.7) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Maximum values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance. The input currents apply for rated power loading (based on Irated) for a line impedance corresponding to uK = 1 %.
5) The specified cable lengths apply to Power Modules without output option and without compliance with the limit values for RI suppression.
Line voltage 500 ... 690 V 3 AC |
PM240P-2 Power Modules |
||||||
---|---|---|---|---|---|---|---|
Without integrated line filter |
6SL3210-1RH25-2UL0 |
6SL3210-1RH26-2UL0 |
6SL3210-1RH28-0UL0 |
6SL3210-1RH31-0UL0 |
6SL3210-1RH31-2UL0 |
6SL3210-1RH31-4UL0 |
|
With integrated line filter |
6SL3210-1RH25-2AL0 |
6SL3210-1RH26-2AL0 |
6SL3210-1RH28-0AL0 |
6SL3210-1RH31-0AL0 |
6SL3210-1RH31-2AL0 |
6SL3210-1RH31-4AL0 |
|
Output current at 50 Hz 690 V 3 AC |
|
|
|
|
|
|
|
|
A |
52 |
62 |
80 |
100 |
115 |
142 |
|
A |
52 |
62 |
80 |
100 |
115 |
142 |
|
A |
42 |
52 |
62 |
80 |
100 |
115 |
|
A |
71 |
84 |
108 |
135 |
156 |
192 |
Rated power |
|
|
|
|
|
|
|
|
kW |
45 |
55 |
75 |
90 |
110 |
132 |
|
kW |
37 |
45 |
55 |
75 |
90 |
110 |
Rated pulse frequency |
kHz |
2 |
2 |
2 |
2 |
2 |
2 |
Efficiency η |
% |
99 |
99 |
99 |
99 |
99 |
99 |
Power loss 3) at rated current |
|
|
|
|
|
|
|
|
kW |
1.08 |
1.3 |
1.37 |
1.75 |
1.95 |
2.49 |
|
kW |
1.09 |
1.31 |
1.38 |
1.76 |
1.97 |
2.51 |
Cooling air requirement |
m3/s (ft3/s) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
0.055 (1.94) |
Sound pressure level LpA (1 m) |
dB |
70.6 |
70.6 |
67.7 |
67.7 |
67.7 |
67.7 |
24 V DC power supply for Control Unit |
A |
1 |
1 |
1 |
1 |
1 |
1 |
Rated input current Irated4) |
A |
50 |
59 |
78 |
97 |
111 |
137 |
Line supply connection U1/L1, V1/L2, W1/L3 |
|
Screw-type terminal |
Screw-type terminal |
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
25 ... 70 |
25 ... 70 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Motor connection U2, V2, W2 |
|
Screw-type terminal |
Screw-type terminal |
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
25 ... 70 |
25 ... 70 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Feedback connection F3, R1 |
|
Screw-type terminal |
Screw-type terminal |
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
25 ... 70 |
25 ... 70 |
35 ... 2 x 120 |
35 ... 2 x 120 |
35 ... 2 x 120 |
35 ... 2 x 120 |
PE connection |
|
Screw-type terminal |
Screw-type terminal |
M10 screw stud |
M10 screw stud |
M10 screw stud |
M10 screw stud |
|
mm2 |
25 ... 70 |
25 ... 70 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
35 ... 120 |
Motor cable length 5), max. |
|
|
|
|
|
|
|
|
m (ft) |
200 (656) |
200 (656) |
300 (984) |
300 (984) |
300 (984) |
300 (984) |
|
m (ft) |
300 (984) |
300 (984) |
450 (1476) |
450 (1476) |
450 (1476) |
450 (1476) |
Degree of protection |
|
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
Dimensions |
|
|
|
|
|
|
|
|
mm (in) |
275 (10.8) |
275 (10.8) |
305 (12.01) |
305 (12.01) |
305 (12.01) |
305 (12.01) |
|
mm (in) |
551 (21.7) |
551 (21.7) |
708 (27.9) |
708 (27.9) |
708 (27.9) |
708 (27.9) |
|
|
|
|
|
|
|
|
|
mm (in) |
237 (9.33) |
237 (9.33) |
357 (14.1) |
357 (14.1) |
357 (14.1) |
357 (14.1) |
|
mm (in) |
274.5 (10.8) |
274.5 (10.8) |
394.5 (15.5) |
394.5 (15.5) |
394.5 (15.5) |
394.5 (15.5) |
Frame size |
|
FSE |
FSE |
FSF |
FSF |
FSF |
FSF |
Weight, approx. |
|
|
|
|
|
|
|
|
kg (lb) |
26 (57.3) |
26 (57.3) |
60 (132) |
60 (132) |
60 (132) |
60 (132) |
|
kg (lb) |
28 (61.7) |
28 (61.7) |
64 (141) |
64 (141) |
64 (141) |
64 (141) |
1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
3) Maximum values. You can find more information on the Internet at https://support.industry.siemens.com/cs/document/94059311
4) The input current depends on the motor load and line impedance. The input currents apply for rated power loading (based on Irated) for a line impedance corresponding to uK = 1 %.
5) The specified cable lengths apply to Power Modules without output option and without compliance with the limit values for RI suppression.
Current derating as a function of the pulse frequency
Rated power |
Rated output current in A for a pulse frequency of |
||||||||
---|---|---|---|---|---|---|---|---|---|
400 V |
460 V |
||||||||
kW |
hp |
2 kHz |
4 kHz |
6 kHz |
8 kHz |
10 kHz |
12 kHz |
14 kHz |
16 kHz |
22 |
25 |
45 |
45 |
38.3 |
31.5 |
27 |
22.5 |
20.3 |
18 |
30 |
30 |
60 |
60 |
51 |
42 |
36 |
30 |
27 |
24 |
37 |
40 |
75 |
75 |
63.8 |
52.5 |
45 |
37.5 |
33.8 |
30 |
45 |
50 |
90 |
90 |
76.5 |
63 |
54 |
45 |
40.5 |
36 |
55 |
60 |
110 |
110 |
93.5 |
77 |
66 |
55 |
49.5 |
44 |
75 |
75 |
145 1) |
145 |
123.3 |
101.5 |
– |
– |
– |
– |
90 |
100 |
178 1) |
178 |
151.3 |
124.6 |
– |
– |
– |
– |
110 |
125 |
205 1) |
143.5 |
– |
– |
– |
– |
– |
– |
132 |
150 |
250 1) |
175 |
– |
– |
– |
– |
– |
– |
1) For these Power Modules, the factory default pulse frequency setting is 2 kHz. If switched over to 4 kHz, the RFI suppression limit values for Category C3 are complied with.
Rated power |
Rated output current in A for a pulse frequency of |
||
---|---|---|---|
690 V |
575 V |
||
kW |
hp |
2 kHz |
4 kHz |
11 |
10 |
14 |
8.4 |
15 |
15 |
19 |
11.4 |
18.5 |
20 |
23 |
13.8 |
22 |
25 |
27 |
16.2 |
30 |
30 |
35 |
21 |
37 |
40 |
42 |
25.2 |
45 |
50 |
52 |
31.2 |
55 |
60 |
62 |
37.2 |
75 |
75 |
80 |
48 |
90 |
100 |
100 |
60 |
110 |
100 |
115 |
69 |
132 |
125 |
142 |
85.2 |
Current derating as a function of ambient temperature
Permissible output current as a function of the ambient temperature for low overload (LO) and high overload (HO)
Note:
The operating temperature ranges of the Control Units should be taken into account. The temperature ranges are specified in the section Technical specifications under Control Units.
Current derating as a function of the installation altitude
Permissible line supplies as a function of the installation altitude
Permissible output current as a function of the installation altitude
Note:
The connected motors, power elements and components must be considered separately.
Current derating as a function of the installation altitude and the ambient temperature
At installation altitudes above 1000 m (3281 ft), the permissible output current can be compensated to a certain extent using the ambient temperature.
Installation altitude above sea level |
Current derating factor (in % of the base-load output current IL) at an ambient temperature of |
||||||||||||
m (ft) |
0 °C (32 °F) |
5 °C (41 °F) |
10 °C (50 °F) |
15 °C (59 °F) |
20 °C (68 °F) |
25 °C (122 °F) |
30 °C (86 °F) |
35 °C (95 °F) |
40 °C (104 °F) |
45 °C (113 °F) |
50 °C (122 °F) |
55 °C (131 °F) |
60 °C (140 °F) |
0 ... 1000 (0 ... 3281) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
93 % |
85 % |
76 % |
66 % |
1000 ... 1500 (3281 ... 4921) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
95 % |
88 % |
81 % |
72 % |
63 % |
1500 ... 2000 (4921 ... 6562) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
97 % |
90 % |
83 % |
77 % |
68 % |
59 % |
2000 ... 2500 (6562 ... 8202) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
98 % |
91 % |
85 % |
79 % |
72 % |
64 % |
56 % |
2500 ... 3000 (8202 ... 9843) |
100 % |
100 % |
100 % |
100 % |
100 % |
98 % |
92 % |
86 % |
80 % |
74 % |
68 % |
60 % |
53 % |
3000 ... 3500 (9843 ... 11483) |
98 % |
98 % |
98 % |
98 % |
98 % |
92 % |
86 % |
81 % |
75 % |
69 % |
64 % |
57 % |
50 % |
3500 ... 4000 (11483 ... 13123) |
91 % |
91 % |
91 % |
91 % |
91 % |
86 % |
81 % |
75 % |
70 % |
65 % |
60 % |
53 % |
46 % |
Installation altitude above sea level |
Current derating factor (in % of the base-load output current IH) at an ambient temperature of |
||||||||||||
m (ft) |
0 °C (32.0 °F) |
5 °C (41.0 °F) |
10 °C (50.0 °F) |
15 °C (59.0 °F) |
20 °C (68.0 °F) |
25 °C (77.0 °F) |
30 °C (86.0°F) |
35 °C (95.0 °F) |
40 °C (104 °F) |
45 °C (113 °F) |
50 °C (122 °F) |
55 °C (131 °F) |
60 °C (140 °F) |
0 ... 1000 (0 ... 3281) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
87 % |
74 % |
1000 ... 1500 (3281 ... 4921) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
95 % |
83 % |
70 % |
1500 ... 2000 (4921 ... 6562) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
99 % |
95 % |
90 % |
78 % |
67 % |
2000 ... 2500 (6562 ... 8202) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
98 % |
94 % |
89 % |
85 % |
74 % |
63 % |
2500 ... 3000 (8202 ... 9843) |
100 % |
100 % |
100 % |
100 % |
100 % |
100 % |
96 % |
92 % |
88 % |
84 % |
80 % |
70% |
59 % |
3000 ... 3500 (9843 ... 11483) |
98 % |
98 % |
98 % |
98 % |
98 % |
94 % |
90 % |
86 % |
83 % |
79 % |
75 % |
65 % |
56 % |
3500 ... 4000 (11483 ... 13123) |
91 % |
91 % |
91 % |
91 % |
91 % |
88 % |
84 % |
81 % |
77 % |
74 % |
70 % |
61 % |
52 % |
Current/power derating as a function of the line voltage
PM240P-2 Power Modules supply a constant power in the line voltage range 380 V to 480 V 3 AC. The constant power results in current derating as a function of the line voltage.
PM240P-2 Power Modules supply a constant output current in the line voltage range 500 V to 690 V 3 AC. Output power derating takes place as a function of the line voltage.
The Power Modules are equipped with an overload reserve e.g. to handle breakaway torques. If larger surge loads occur, this must be taken into account in the configuration. For drives with overload requirements, the appropriate base-load current must, therefore, be used as a basis for the required load.
The units can operate in two different duty cycles in the permissible continuous operating range. Depending on how the system is dimensioned, the relevant base-load current is effective as a rated quantity.
The criterion for overload is that the inverter is operated with its base-load current before and after the overload occurs on the basis of a duty cycle duration of 300 s.
The base-load current IL for low overload is the basis for a duty cycle of 135 % for 3 s plus 110 % for 57 s.
The base-load current IH for a high overload is based on a duty cycle of 150 % for 60 s.
Overload capability, low overload
Overload capability, high overload
Principle dimension drawing and drill pattern for PM240P-2 Power Module
Frame size |
Dimensions in mm (inches) |
Drilling dimensions in mm (inches) |
Cooling clearance in mm (inches) |
Mounting |
||||||
---|---|---|---|---|---|---|---|---|---|---|
|
a |
b |
c |
d |
e |
f |
top |
bottom |
front |
With bolts |
PM240P-2 Power Modules |
||||||||||
FSD |
200 |
472 |
237 |
170 |
430 |
15 |
300 |
350 |
100 |
4 × M5 |
FSE |
275 |
551 |
237 |
230 |
509 |
11 |
300 |
350 |
100 |
4 x M6 |
FSF |
305 |
708 |
357 |
270 |
680 |
13 |
300 |
350 |
100 |
4 × M8 |
1) Increase in Power Module mounting depth:
• When the CU230P‑2 Control Unit is plugged on, the depth increases by 15.5 mm (0.61 in)
• When the IOP is plugged on, the depth increases by a further 22 mm (0.87 in)
• When the BOP‑2 is plugged on, the depth increases by a further 11 mm (0.43 in)
(Nguyễn Thảo Trường - http://DienElectric.com theo Siemens)