General specifications | ||
---|---|---|
Signal type | Analog input | |
Operation time | MTBF: 272 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
|
Supply | ||
Connection | Power Bus or terminals 1-, 2+ | |
Rated voltage | 16.8 ... 31.2 V DC | |
Power dissipation | 0.8 W | |
Power consumption | 1.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 5+, 6- | |
Input signal | 0/4 ... 20 mA 0/2 ... 10 V |
|
Open circuit voltage/short-circuit current | ≤ 22 V / 35 mA | |
Input resistance | ≤ 25 Ω | |
Transmission range | linearity range: -1 ... 110 % | |
Available voltage | 16 V at 20 mA | |
Output | ||
Connection side | control side | |
Ripple | ≤ 10 mV eff | |
Output I | ||
Connection | terminals 3-, 4+ | |
Output signal | 0/1 ... 5 V, 0/2 ... 10 V , load ≥ 5 kΩ 0/4 ... 20 mA , load ≤ 300 Ω |
|
Output II | ||
Connection | terminals 7+, 8- | |
Output signal | 0/1 ... 5 V, 0/2 ... 10 V , load ≥ 5 kΩ 0/4 ... 20 mA , load ≤ 300 Ω |
|
Transfer characteristics | ||
Accuracy | max. 0.1 % of full-scale value | |
Influence of ambient temperature | < 100 ppm/K of full-scale value | |
Frequency range | 0 ... 100 Hz | |
Rise time/fall time | ≤ 3.5 ms | |
Galvanic isolation | ||
Output/power supply | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Input/Other circuits | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Output I/II | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | EN 61010-1:2010 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
Mass | approx. 70 g | |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 | |
Height | 97 mm | |
Width | 6.2 mm | |
Depth | 107 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | DEMKO 16 ATEX 1750X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 | |
IECEx approval | ||
IECEx certificate | IECEx UL 16.0116X | |
IECEx marking | Ex nA IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210119 |
ECLASS 12.0 | 27210119 |
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |