Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
Width | 6.2 mm |
Height | 93.1 mm |
Depth | 102.5 mm |
Ambient temperature (operation) | -20 °C ... 65 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Maximum altitude | ≤ 2000 m |
Number of inputs | 1 |
Configurable/programmable | no |
Voltage input signal | 0 V ... 10 V |
max. input voltage | 30 V |
Input resistance of voltage input | approx. 100 kΩ |
Number of outputs | 1 |
Configurable/programmable | no |
Current output signal | 4 mA ... 20 mA |
Max. output current | 28 mA |
Load/output load current output | ≤ 500 Ω |
Ripple | < 20 mVPP (at 500 Ω) |
Nominal supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 20 mA |
Power consumption | < 450 mW |
Connection method | Screw connection |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Stripping length | 12 mm |
Screw thread | M3 |
No. of channels | 1 |
Maximum transmission error | ≤ 0.1 % (of final value) |
Maximum temperature coefficient | < 0.01 %/K |
Temperature coefficient, typical | < 0.002 %/K |
Limit frequency (3 dB) | approx. 100 Hz |
Step response (10-90%) | approx. 3.5 ms |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 30 V AC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 | |
GL | GL EMC 2 D |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 5 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 5 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 5 % |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T4 | |
GL | GL EMC 2 D |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2 |
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 4.0 | 27210120 |
eCl@ss 4.1 | 27210120 |
eCl@ss 5.0 | 27210120 |
eCl@ss 5.1 | 27210120 |
eCl@ss 6.0 | 27210120 |
eCl@ss 7.0 | 27210120 |
eCl@ss 8.0 | 27210120 |
eCl@ss 9.0 | 27210120 |
ETIM 4.0 | EC002653 |
ETIM 5.0 | EC002653 |
ETIM 6.0 | EC002653 |
UNSPSC 6.01 | 30211506 |
UNSPSC 7.0901 | 39121008 |
UNSPSC 11 | 39121008 |
UNSPSC 12.01 | 39121008 |
UNSPSC 13.2 | 39121008 |